TEMA / Heat Transfer · Engineering tool

Heat exchanger LMTD

Q = U · A · F · LMTD

Shell-and-tube duty or area from the log-mean temperature difference — counterflow LMTD with a correction factor.

Run the calculation

Live calculator

Run the calculation

LMTDHeat Transfer

Duty Q

208.6kW

LMTD
69.5°C
ΔT1
80.0°C
ΔT2
60.0°C
Correction factor F
1
Heat-transfer area
10m²
Valid counterflow configuration — LMTD computed.

How it works

The log-mean temperature difference (LMTD) is the effective driving temperature for a heat exchanger. For counterflow, LMTD = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2), where ΔT1 and ΔT2 are the hot/cold terminal temperature differences at each end.

The duty is Q = U·A·F·LMTD, where U is the overall heat-transfer coefficient, A the heat-transfer area, and F a correction factor accounting for non-counterflow arrangements (1.0 for true counterflow; read from a correction-factor chart for 1-2, 2-4, etc.).

This tool computes the counterflow LMTD and either the duty (given U, A, F) or the required area (given a target duty). U and F come from the exchanger geometry and stream properties — this tool does not rate a specific unit.

Assumptions & limitations

  • Steady-state, no phase change unless the terminal ΔTs reflect it; constant U and cp across the exchanger.
  • Counterflow LMTD. For shell-and-tube arrangements apply the correction factor F (≤1); F ≈ 1 for pure counterflow and falls off near a temperature cross.
  • Terminal temperatures must be monotonic (no temperature cross); if ΔT1 or ΔT2 ≤ 0 the configuration is infeasible.
  • Overall U and F are user inputs; this tool does not compute film coefficients, fouling, or shell/tube geometry rating.